Temp-O-Matic Oil Furnace
TMP Multi-Position (Counterflow / Horizontal)
Furnace Manual
Contents Page
Read this first!............................................................................ 2
1. Check furnace location .............................................................. 3
2. Prepare furnace and place in position ....................................... 6
3. Connect supply and return ducts............................................... 8
4. Venting..................................................................................... 11
5. Connect fuel oil piping ............................................................. 12
6. Wire furnace and burner .......................................................... 14
7. Start-up .................................................................................... 17
8. Checkout procedure ................................................................ 18
9. Troubleshooting....................................................................... 19
10. Service and maintenance ........................................................ 20
11. Components and replacement parts........................................ 23
12. Dimensions and ratings ........................................................... 25
13. Owner’s information................................................................. 27
Hazard definitions
Hazards that will cause severe personal injury,
death or substantial property damage.
Hazards that can cause severe personal injury,
death or substantial property damage.
Hazards that will or can cause minor personal
injury or property damage.
Special instructions on installation, operation or
maintenance that are important but not related to
personal injury or property damage.
INSTALLER – Read all instructions before
installing. Read page 2 first. Follow all instructions
in proper order to prevent personal injury or death.
Consider ducting, fuel supply, venting and
installation when determining furnace location.
Any claims for damage or shortage in shipment
must be filed immediately against the transportation
company by the consignee.
Do not store or use gasoline or other flammable
liquids or vapors near this furnace or any other
appliance.
Ventilate house while operating furnace for the first
time. Odors may be emitted for a brief period.
Do not alter this furnace in any way. The
manufacturer will not be liable for any damage
resulting from changes made in the field to the
furnace or its components or from improper
installation. Failure to comply could result in severe
personal injury, death or substantial property
damage.
USER – Please read the following. Failure to
comply could result in severe personal injury, death
or substantial property damage.
This manual is for use only by your qualified
heating installer / service technician.
Please see the Owner’s information only, on back
page of this manual.
Have the furnace serviced by a qualified service
technician, at least annually.
This manual must only be used by a qualified
heating installer / service technician. Furnace and
burner must be installed and serviced only by a
qualified heating installer / service technician.
Failure to comply could result in severe personal
injury, death or substantial property damage.
When calling or writing about the furnace – Please
indicate furnace model number and serial number
from rating label. You may list the serial number and
model number in the space provided on the
“Installation and service certificate” found on
page 18.
KEEP THESE INSTRUCTIONS
WITH FURNACE FOR FUTURE
REFERENCE.
Vista de página 0
1 2 3 4 5 6 ... 27 28

Resumo do Conteúdo

Página 1 - Furnace Manual

Printed on 100% recycled paper 670-000-004/1010 Temp-O-Matic Oil Furnace TMP Multi-Position (Counterflow / Horizontal) Furnace Manual Content

Página 2 - READ THIS FIRST!

TMP Oil Furnaces – Furnace Manual 10 670-000-004/1010 3 Connect supply and return ducts (continued) Duct sizing (continued) Table 5 Typical du

Página 3 - 1 Check furnace location

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 11 4 Venting General venting requirements Failure to follow all instructions can result in

Página 4

TMP Oil Furnaces – Furnace Manual 12 670-000-004/1010 5 Connect fuel oil piping General oil piping requirements • Location and installation of o

Página 5

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 13 Notes:

Página 6

TMP Oil Furnaces – Furnace Manual 14 670-000-004/1010 6 Wire furnace & burner Electric shock hazard. It can cause severe personal injury or de

Página 7

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 15 6 Wire furnace & burner (continued) PLB Oil Furnaces – Furnace Manual Figure

Página 8

TMP Oil Furnaces – Furnace Manual 16 670-000-004/1010 6 Wire furnace & burner (continued) PLB Oil Furnaces – Furnace Manual Figure

Página 9

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 17 Gasket for overfire pressure reading 7 Start up Follow information below to prevent seve

Página 10 - – Furnace Manual

TMP Oil Furnaces – Furnace Manual 18 670-000-004/1010 8 Checkout procedure Furnace selection  ..1. Heat loss ... BTU

Página 11 - 4 Venting

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 19 9 Troubleshooting Check

Página 12 - 5 Connect fuel oil piping

2 670-000-004/1010 READ THIS FIRST! Failure to adhere to the guidelines below can result in severe personal injury, death or substan

Página 13

TMP Oil Furnaces – Furnace Manual 20 670-000-004/1010 10 Service and maintenance Follow the “Service and maintenance” procedures given throughout

Página 14 - 6 Wire furnace & burner

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 21 Handling ceramic fiber and fiberglass materials HANDLING OR REMOVAL OR COMBUSTION CHAMBER

Página 15

TMP Oil Furnaces – Furnace Manual 22 670-000-004/1010 10 Service and maintenance (continued) To lubricate and inspect blower motor DO NOT lubricat

Página 16 - PLB

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 23 11 Components and replacement parts Figure 7 Model TMP furnaces – Component locations B

Página 17 - 7 Start up

TMP Oil Furnaces – Furnace Manual 24 670-000-004/1010 B50098 Rev.B ITEM DESCRIPTION PART #1Complete heat exchanger (item 2, 3, 4, 5 & 6 include

Página 18 - 8 Checkout procedure

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 25 12 Dimensions and ratings Figure 5 Model TMP dimensional data – ALL DIMENSIONS IN INCHE

Página 19 - 9 Troubleshooting

TMP Oil Furnaces – Furnace Manual 26 670-000-004/1010 12 Dimensions and ratings Model TMP-105, Burners data Air

Página 20 - 10 Service and maintenance

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 27 13 Owner’s information The furnace must be inspected and started ANNUALLY, at the beginn

Página 21

TMP Oil Furnaces – Furnace Manual X40105 Rev. K

Página 22 - To start furnace

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 3 1 Check furnace location Pre-installation checklist Verify code compliance  Local, state

Página 23

TMP Oil Furnaces – Furnace Manual 4 670-000-004/1010 1 Check furnace location (continued) Air for combustion and ventilation Adequate combustio

Página 24

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 5 1 Check furnace location (continued) Air contamination Please review the following informa

Página 25 - 12 Dimensions and ratings

TMP Oil Furnaces – Furnace Manual 6 670-000-004/1010 2 Prepare furnace and place in position Inspect & prepare furnace Remove furnace from c

Página 26

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 7 2 Prepare furnace and place in position (continued) Blocked Vent Shut-Off (BVSO) for chim

Página 27 - 13 Owner’s information

TMP Oil Furnaces – Furnace Manual 8 670-000-004/1010 3 Connect supply and return ducts Duct sizing Determine airflow CFM The temperature rise th

Página 28

TMP Oil Furnaces – Furnace Manual 670-000-004/1010 9 3 Connect supply and return ducts (continued) Duct sizing (continued) Table 4 Typical d